In Part 1, we talked about why coordination was needed? In Part 2, we will talk about the different components of a power system and the reason why coordination works.

In this facility, we have a utility source generating power at 13.8 KV which is feeding a 1 MVA transformer. The transformer then steps the voltage down to 4.16 kV which feeds a downstream 4.16 KV bus. There is also a 100 Ampere breaker which we will name “Breaker A”. There is another 4.16 KV emergency generator, which feeds the 4.16 KV bus through a tie breaker.

We also have a few medium voltage motors connected to the 4.16 KV bus through feeder breakers. Additionally, we have a 20 Amp fuse which is serving as a feeder. This fuse is feeding a 100 KVA transformer which steps the voltage down further from 4.16 KV to 480 volts. We also have a 120 Amp breaker which we’ll name “Breaker B” which is connected to a 480 volt bus. This 480 volt bus is feeding a low voltage motor through a third breaker which we will call “Breaker C”.

Before we talk about intricacies of how coordination is actually performed, let’s first understand the general structure of this power system. Under normal operating conditions, the tie breaker connected to the generator bus would be open and interlocked as the system is powered by the utility bus through the utility transformer.

If we look at the sizing of each breakers, we can clearly see that the highest rated breakers are connected to the upstream 13.8 KV bus. The second highest rated breakers are connected to the 4.16 KV buses. And the third highest rated breakers are connected to the 480 volt bus.

Intuitively speaking, we should typically expect upstream breakers to be greater than the downstream breaker for which we’d like to coordinate with.

If Breaker C is sized at 80 Amps, then then we should expect Breaker B to be greater than 80A… As expected, Breaker B is rated at 120 Amps in our example. And if we consider Breaker A which has a rating of 100 Amps at 4.16 KV, then breaker B should typically be sized smaller. Again, Breaker B is rated for 120 Amps at 480V. If we compare both breaker ratings at a common voltage, the difference is much greater.

So to summarize it all, as a rule of thumb, we should typically expect breakers sized in reference to their downstream or upstream breakers.

In part 3, we shall talk about the goals and strategies of protective device co-ordination.

Greetings from the GeneralPAC Team!

We make high-quality Power Systems Video Tutorials on complex topics that are free and open to everyone!  Thank you so much for supporting us through Patreon so can continue doing good and valuable work.

What is Patreon and why do we use it?

Patreon is a fantastic portal that allows our fans and community to make monthly contribution (like Netflix subscription) so we can continue creating high-quality power systems video tutorials. In return, you get access to incredible perks like voting on future topics, getting your questions answered, access to VIP Q/A webinars with the creators of GeneralPAC, and much more! We THANK YOU for supporting us

Why do we need your support?

An incredible amount of time and effort is needed to develop high-quality video tutorials. Each video (Part 1 for example) takes approximately 10 hours to complete which includes learning the concept ourselves, brainstorming creative ways to teach and explain the concepts, writing the script, audio recording, video recording, and editing. It's no wonder why Hundreds-of-Thousands of people have watched, liked, subscribed, and left positive comments on Youtube channel. Your support truly makes all the difference.

Become a patron today!